JCB2LE-EV RCBO Type EV 1P+N
Electronic Type
Ea rth leaka ge protection
Overloa da nd short circuit protection
Brea king ca pa city 6 ka (6 A to 40A ca n be up gra ded to 10 kA) Rated current up to 40A (available from 6A to 40A) Type EVareavaiable
Tripping sensitivity:30mA,100mA
Double pole switching for complete is olation of fa ulty cir cuits Neutra l pole switching significa ntly reduces the insta llation and commissioning test time
Complies with IEC61009-1.EN61009-1
Interna lly equipped with physica | brea k points
Features
Electronic Type
Ea rth leaka ge protection
Overloa da nd short circuit protection
Brea king ca pa city 6 ka (6 A to 40A ca n be up gra ded to 10 kA) Rated current up to 40A (available from 6A to 40A) Type EVareavaiable
Tripping sensitivity:30mA,100mA
Double pole switching for complete is olation of fa ulty cir cuits Neutra l pole switching significa ntly reduces the insta llation and commissioning test time
Complies with IEC61009-1.EN61009-1
Interna lly equipped with physica | brea k points
Application
The JCB2LE- EV RCBOs (residual current circuit brea ker with overload protection) are suitable for consumer units or distribution boards, applied under occasions such as industrial, a nd commercial, high- rise buildings and residential houses
Switched Live and Neutral
JCB2 LE- EV rcbo with swltched neutal built in as standard will fully isolate a faulty or damaged circult by dlsconnecting live and neutral conductors. They offers the most comprehenswe circult protection avalable
Technical Data
| Product code | JCB2LE-EV | |
| Standard | IEC61009-1, EN61009-1 | |
| Electrical features | Rated current In (A) | 6, 10, 16, 20, 25, 32, 40, 63 |
| Type | Electronic | |
| Type(wave from of the earth leakage sensed) | A are available | |
| Poles | 2Pole | |
| Rated voltage Ue (V) | 230/240 | |
| Rated sensitivity IΔn | 30mA, 100mA, 300mA | |
| Insulation voltage Ui (V) | 500 | |
| Rated frequency | 50/60Hz | |
| Rated breaking capacity | 6KA | |
| Rated impulse withstand voltage (1.2/50) Uimp (V) | 6,000 | |
| Dielectric test voltage at ind.Freq. for 1 min (KV) | 2 | |
| Pollution degree | 2 | |
| Thermo-magnetic release characteristic | B, C | |
| Mechanical features | Electrical life | 2,000 |
| Mechanical life | 10,000 | |
| Contact position indicator | Yes | |
| Protection degree | IP20 | |
| Reference temperature for setting of thermal element(℃) | 30 | |
| Ambient temperature(with daily average ≤35℃) | -5…+40 | |
| Storage temperature(℃) | -25…+70 | |
| Installation | Terminal connection type | Cable/U-type busbar/Pin-type busbar |
| Terminal size top/bottom for cable | 25mm2/18-3AWG | |
| Terminal size top/bottom for Busbar | 10mm2/18-8AWG | |
| Tightening torque | 2.5N*m/22In-lbs | |
| Mounting | On DIN rail EN 60715(35mm) | |
| Connection | From top or bottom are available | |